Technical Statement
Product Description
Flexible design for implementing decentralized, central and combined systems.
• AdComNet bus system for seamless networking of two or more CPS-M1 control panels
• Incorporated failsafe 72-hour battery backup
• Auto
close on loss of power functionality to ensure that windows or louvres are
never stuck open during a power failure
• BMS integration can accommodate both high level (modbus, KNX or BacNet) and low level
integration with third party systems
• Tested and certified to ISO 21927‑9, VdS 2581, VdS 2593, VdS 2344, DIN EN 12101‑10 and EN 62368-1:2014 + A11:2017
• Exact
position feedback of drives through ACB technology
• Integration of internal
& external temperature, Co2, wind & rain, wind & directional
sensors including FIP activation
• Configurable smoke and ventilation functions using D+H software SCS
• Control panel housing steel sheet in varies sizes
• Control panel housing is lockable
Scope of use
Ventilation Type
Smoke Ventilation: Used to control smoke and heat ventilation actuator drives in the event of a fire, improving safety and reducing damage
Natural Ventilation:
Used to control actuator drives for natural airflow for daily ventilation , enhancing indoor air quality and comfort
Control Zones
Controls Varies Zones: Determine how many zones need to be controlled based on the building layout and ventilation requirements
Products to be controlled by the CPS-M1-S Control Panel
Chain Drive Actuators: Ideal for window automation, providing precise control for natural & smoke ventilation.
Linear Actuators: Suitable for automating louvres, operable windows, operable ventilators & skylights.
Locking Drives: Ensure secure closure of windows and louvres.
Weather Sensors: Monitor environmental conditions to optimise ventilation.
Building Management Systems (BMS): Integrate and control various building systems for efficiency and comfort.
New Zealand Building Code (NZBC)
The product will, if employed in accordance with the supplier's installation and maintenance requirements, assist with meeting the following provisions of the building code:
- Clause C5 Access and safety for fire fighting operations: Performance C5.7, C5.7(b), C5.8
EN 12101-10: This standard pertains to smoke and heat control systems. Specifically, Part 10 focuses on power supplies. Compliance with EN 12101-10 ensures that control panels used in smoke and heat control systems meet the necessary safety and performance requirements.
ISO 21927-9: another standard related to smoke and heat control systems. In this case, Part 9 specifies requirements for control equipment. Compliance with ISO 21927-9 ensures that the control equipment—such as control panels—meets international standards for functionality, reliability, and safety.
- Clause F7 Warning systems: Performance F7.3.3
Battery Backup (Standby Power): Having a battery backup system with a standby power duration of 72 hours is essential. During power outages or emergencies, this backup power ensures that the smoke and heat control system remains operational. It allows for continued ventilation, smoke extraction, and fire safety measures even when the main power supply fails.
Auto Close on Loss of Power: This feature is critical for safety. When the main power supply is lost, the smoke control system will automatically close dampers, louvres, or other ventilation openings. This action prevents smoke from spreading throughout the building and helps maintain safe evacuation routes.
Line Monitoring for Field Cabling: Monitoring the field cabling is essential for fire safety. By continuously checking the integrity of cabling connections, faults or damage can be detected promptly. This monitoring ensures that the smoke and heat control system remains fully functional and reliable.
- Clause G4 Ventilation: Performance G4.3.1
Natural Ventilation: Designed to control automated 24v/dc equipment for the purpose for natural ventilation in buildings, contributing to architectural sustainability.
Integrated sensors including internal & external temperature / Co2 / Rain / Wind & Speed are all powered by the control panel, the control panel uses algorithms to provided opening positions to maximise internal and external weather conditions
Notes
C5.7 -Control panel indicates which zone is in a fire condition.
-Control panel switches provide the ability for firefighter to open or close automated windows or louvres in a fire condition.
C5.7(b) - Control panels have indication switches provided that have light indication of active fire mode or standby mode.
- Control panels are operated by onsite FIP panels to activate in fire mode.
C5.8 - Control panels provide the operation to ventilate smoke out the building and this creates a visual path for people and fire fighters to leave and access the building.
- Control panels are provided with fail safe 72-hours of standby battery backup.
F7.3.3 - Control panels when selected can be provided with audial alarms in fire condition
G4.3.1 - Control panels provide feedback from internal & external temperature and Co2 sensors to power automated windows/louvres to open or close.
Evidence
The product meets the requirements set out in the following documents, or relevant parts of cited standards within the documents:
Tested and certified according to International Standards:
ISO 21927‑9, VdS 2581, VdS 2593, VdS 2344, DIN EN 12101‑10 and EN 62368-1:2014 + A11:2017, fulfils the building authority requirements in accordance with DIN 18232-9
EN 12101-10 Smoke and heat control systems - Part 10: Power supplies
ISO 21927-9 Smoke and heat control systems — Part 9: Specification for control equipment
Supporting evidence
The product has and can make available the following additional evidence to support the above statements:
Use in Service History
D+H has been suppling control panels / automated chain & linear actuators into New Zealand estimated 20 years.
EBSA established in New Zealand 8 years ago, EBSA is a licenced partner to distribute / commission / maintain and service all imported D+H products.
Product Criteria
Design requirements
Ventilation Type
Smoke Ventilation: Used to control smoke and heat ventilation actuator drives in the event of a fire, improving safety and reducing damage
Natural Ventilation: Used to control actuator drives for natural airflow for daily ventilation , enhancing indoor air quality and comfort
Control Zones
Controls Varies Zones: Determine how many zones need to be controlled based on the building layout and ventilation requirements
Products to be controlled by the CPS-M1-S Control Panel
Chain Drive Actuators: Ideal for window automation, providing precise control for natural & smoke ventilation.
Linear Actuators: Suitable for automating louvres, operable windows, operable ventilators & skylights.
Locking Drives: Ensure secure closure of windows and louvres.
Weather Sensors: Monitor environmental conditions to optimise ventilation.
Building Management Systems (BMS): Integrate and control various building systems for efficiency and comfort.
Installation requirements
Installation Requirements
Do not commence installation unless all preparatory work is of the required standard.
Anchor control panel to the specified location.
Confirm if it will be top or bottom entry for field cable connections
Remove the necessary amount of cable glands at the top or bottom of the control panel to allow for the field cabling to be installed in the control panel.
A 240VAC supply is to be isolated locally at each panel and terminated inside each panel, this is to be supplied and installed by an electrical sub-contractor
Maintenance requirements
Ensure the batteries are functioning correctly by performing a load test.
Verify that all cables are securely connected and have not come loose.
Check that the control panel housing is secure and can be locked properly.
Conduct a thorough test of the control panel and all connected devices to ensure they are operating correctly.
Warrantees
3 year manufactures warranty
5 years installation warranty
Environmental
Sheet steel housing, various sizes due to modular design per project bases.
Electrical components & modules
The service life of electrical control units for SHEV and ventilation systems from D+H Mechatronic AG is optionally specified at 25 years according to the manufacture.
The reference service life is for the features, which are reported in the EPD report.
Contact EBSA for EPD (Environmental Product Declaration)
Quality Assurance
|
ISO 9001 (Quality Management) |
Relationships
|
IFT Rosenheim
M-EPD-SVR-GB-103 |
Building Product Information Requirements
Manufacturer
Legal Trading Name:
D+H Mechatronic AG
Contact Number/s:
+494 0605650
Importer
Legal Trading Name:
EBSA NZ Limited
Business Email:
sales@ebsa.co.nz
Contact Number/s:
09 8840025
Product Identifier
CPS-M1-S CPS-M1-020 / 040 / 060 / 080
Warnings
This product has no warnings associated with it.