Compliance Statement
Scope of Use
Hallmark Europa Fire Doors, for use as
fire rated doorsets with a maximum achievable fire rating of up to 240min (Integrity)
and a 60min Insulation rating where required. Manufactured with E-Core® solid
vermiculite mineral core. Available as single or double doors, hinged or double
action pivot.
Hallmark Europa Fire Doors are custom
fabricated to the requirements of each project including door leaf sizes, Fire
Resistance Rating (FRR), smoke seals, timber or steel door frame, customized door leaf facings, leaf edge options, vision panel,
vision panel beading options, side lights, overpanels, ventilation grills and acoustic
rating.
New Zealand Building Code (NZBC)
The product will, if employed in accordance with the supplier's installation and maintenance requirements, assist with meeting the following provisions of the building code:
- Clause B2 Durability: Performance B2.3.1(b)
• Hallmark Doors have a durability beyond 15 years when correctly installed
and maintained, based on historic use in-market for more than 30 years.
• Hallmark Europa Fire Doors, where glazed, contain glass that has been
tested and meets the requirements of BS EN 12600:2002 and BS EN 1288 Glass in
Building. Determination of the bending strength of glass.
• Hallmark Europa Fire Doors will satisfy the requirements
of NZBC, B2 Durability under conditions of use, and Care of Product as detailed
by Hallmark Group or otherwise specified within contractual guarantees. - Clause C3 Fire affecting areas beyond the fire source: Performance C3.6, C3.7, C3.9
In accordance with NZBC C/AS2 clause 4.16 and Appendix C
clause C6.1.1, Hallmark Europa Fire Doors comply with NZS 4520 and are tested
to AS 1530.4. Fire doors are supplied
with Product Labels/ID tags which comply with NZS 4520, on which the Fire
Resistance Rating (FRR) and door set numbers are detailed. In accordance with
NZS 4520, Hallmark Group maintains a register of door sets, and issues an
installer’s declaration with each door set.
• Hallmark Europa doors to be fitted with smoke seals in
accordance with NZBC C/AS2 clause 4.16.2 b) and Appendix C C6.1.2.
• If required, glazing to Hallmark Europa Fire Doors is in
accordance with NZBC C/AS2 paragraph 4.2, uninsulated and insulated vision comply
with NZS 4520.
• Hallmark Europa Fire Doors are to be self-latching, in
accordance with NZS 4520. The selection of hardware
to meet these requirements is not the responsibility of Hallmark Group but Hallmark
Group makes available a list of commonly specified and approved hardware for
use with its fire door set products.
• Hallmark Europa Fire Doors are to be self-closing in
accordance with NZBC C/AS2 Appendix C, clause C6.1.4 and C6.1.5. If door is located on an escape route, a
self-closing device to be installed and adjusted to meet maximum frictional
forces requirements of NZBC C/AS2 Appendix C, clause 6.1.3. The selection of hardware to meet these requirements is not
the responsibility of Hallmark Group but Hallmark Group
makes available a list of commonly specified and approved hardware for use with
its fire door set products.
• Doors subdividing escape routes, to be designed in
accordance with NZBC C/AS2 clause 3.15, including door closers and latching,
locking devices, direction of opening, degree of opening, vision panels, hold
open devices, delayed action unlocking devices and panic fastenings. The selection of hardware to meet these requirements is not
the responsibility of Hallmark Group but Hallmark Group
makes available a list of commonly specified approved hardware for use with its
fire door set products. - Clause C4 Movement to place of safety: Performance C4.3, C4.4, C4.5
In accordance with NZBC C/AS2 clause 4.16 and Appendix C clause C6.1.1, Hallmark Europa Fire Doors comply with NZS 4520 and are tested to AS 1530.4. Fire doors are supplied with Product Labels/ID tags which comply with NZS 4520, on which the Fire Resistance Rating (FRR) and door set numbers are detailed. In accordance with NZS 4520, Hallmark Group maintains a register of door sets, and issues an installer’s declaration with each door set.
• Hallmark Europa doors to be fitted with smoke seals in accordance with NZBC C/AS2 clause 4.16.2 b) and Appendix C C6.1.2.
• If required, glazing to Hallmark Europa Fire Doors is in accordance with NZBC C/AS2 paragraph 4.2, uninsulated and insulated vision comply with NZS 4520.
• Hallmark Europa Fire Doors are to be self-latching, in accordance with NZS 4520. The selection of hardware to meet these requirements is not the responsibility of Hallmark Group but Hallmark Group makes available a list of commonly specified and approved hardware for use with its fire door set products.
• Hallmark Europa Fire Doors are to be self-closing in accordance with NZBC C/AS2 Appendix C, clause C6.1.4 and C6.1.5. If door is located on an escape route, a self-closing device to be installed and adjusted to meet maximum frictional forces requirements of NZBC C/AS2 Appendix C, clause 6.1.3. The selection of hardware to meet these requirements is not the responsibility of Hallmark Group but Hallmark Group makes available a list of commonly specified and approved hardware for use with its fire door set products.
• Doors subdividing escape routes, to be designed in accordance with NZBC C/AS2 clause 3.15, including door closers and latching, locking devices, direction of opening, degree of opening, vision panels, hold open devices, delayed action unlocking devices and panic fastenings. The selection of hardware to meet these requirements is not the responsibility of Hallmark Group but Hallmark Group makes available a list of commonly specified approved hardware for use with its fire door set products. - Clause C5 Access and safety for fire fighting operations: Performance C5.6, C5.8
In accordance with NZBC C/AS2 clause 4.16 and Appendix C clause C6.1.1, Hallmark Europa Fire Doors comply with NZS 4520 and are tested to AS 1530.4. Fire doors are supplied with Product Labels/ID tags which comply with NZS 4520, on which the Fire Resistance Rating (FRR) and door set numbers are detailed. In accordance with NZS 4520, Hallmark Group maintains a register of door sets, and issues an installer’s declaration with each door set.
• Hallmark Europa doors to be fitted with smoke seals in accordance with NZBC C/AS2 clause 4.16.2 b) and Appendix C C6.1.2.
• If required, glazing to Hallmark Europa Fire Doors is in accordance with NZBC C/AS2 paragraph 4.2, uninsulated and insulated vision comply with NZS 4520.
• Hallmark Europa Fire Doors are to be self-latching, in accordance with NZS 4520. The selection of hardware to meet these requirements is not the responsibility of Hallmark Group but Hallmark Group makes available a list of commonly specified and approved hardware for use with its fire door set products.
• Hallmark Europa Fire Doors are to be self-closing in accordance with NZBC C/AS2 Appendix C, clause C6.1.4 and C6.1.5. If door is located on an escape route, a self-closing device to be installed and adjusted to meet maximum frictional forces requirements of NZBC C/AS2 Appendix C, clause 6.1.3. The selection of hardware to meet these requirements is not the responsibility of Hallmark Group but Hallmark Group makes available a list of commonly specified and approved hardware for use with its fire door set products.
• Doors subdividing escape routes, to be designed in accordance with NZBC C/AS2 clause 3.15, including door closers and latching, locking devices, direction of opening, degree of opening, vision panels, hold open devices, delayed action unlocking devices and panic fastenings. The selection of hardware to meet these requirements is not the responsibility of Hallmark Group but Hallmark Group makes available a list of commonly specified approved hardware for use with its fire door set products. - Clause D1 Access routes: Performance D1.3.1(b), D1.3.1(c), D1.3.4(f)
• Hallmark Europa Fire Doors can be used within as
accessible route where design consideration is given to compliance to NZBC
D1/AS1, paragraph 7.0.
• Doors to be installed with door handles that meet the
requirements of NZBC D1/AS1 clause 7.0.5.
The selection
of hardware to meet these requirements is not the responsibility of Hallmark
Group but Hallmark Group makes available a list of commonly specified
approved hardware for use with its fire door set products. - Clause E2 External moisture: Performance E2.3.2, E2.3.7
• Hallmark Europa Fire Doors have not been tested for water
ingress in exterior installations and we make no statement as to its suitability
under NBCC E2 “External Moisture”. All exterior doors should be given as much
shelter as permissible and be fitted with appropriate flashing systems. - Clause F2 Hazardous building materials: Performance F2.3.2, F2.3.3
- Hallmark Doors are manufactured using inert, nontoxic
materials
-
Hallmark Europa Fire Doors contain no Asbestos, Crystalline
Silica or other inorganic fibers.
- If required, Hallmark Europa Fire Door
vision panels, side lights and overpanels, glazing complies with NZS 4223.3.
Evidence
The product meets the requirements set out in the following documents, or relevant parts of cited standards within the documents:
• NZS
4520:2010 Fire resistant doorsets
• AS 1530.4:2005
& 2014 Methods for fire tests on building materials, components and
structures. Part 4: Fire resistance
tests of elements of building construction.
• NZS 4223.3:
2016 Code of practice for glazing in buildings Part 3: Human impact safety
requirements
• BS EN
12600:2002 Glass in Building. Pendulum test. Impact test method and
classification for flat glass.
• BS EN 1288 Glass in
Building. Determination of the bending strength of glass.
Design requirements
- Hallmark Europa Fire Doors are designed for commercial and
residential buildings, and their associated ancillary and outbuildings.
- Maximum door leaf heights and widths, required door leaf thicknesses
are stated on the door data sheets.
- Door frames, Door leaf facing options, Design door vision
panels, side lights and overpanels, Ventilation grilles, to be in accordance
with options stated on the selected door data sheets.
- All hardware used in conjunction with Hallmark Europa Fire
Doors to be Hallmark Group approved hardware. The selection of hardware is not the
responsibility of Hallmark Group but Hallmark Group makes available a list
of commonly specified approved hardware for use with its fire door set
products.
- For compliance fire signage to be installed in conjunction
with fire doors in accordance with NZBC C/AS2, paragraph 3.16 and F8/AS1,
paragraph 5.2.
- Refer to www.hallmarkgroup.co.nz/fire-doors for Hallmark
Europa Fire Door data sheets.
Installation requirements
- Inspect products prior to installation to ensure they are free from
defects.
- Hallmark Fire Doors must be installed in accordance with Hallmark
requirements. Refer to www.hallmarkgroup.co.nz/fire-door-installation.
- Opening to be prepared as per Hallmark Group Installation
Document relating to correct configuration and wall system.
- Appropriate packers and Backfilling required to ensure
compliance, generally maximum 10mm thick, see appropriate Installation Document
- Fix Jamb as per appropriate requirements, see appropriate Installation Document
- Where doorstops are supplied loose (Timber Jamb System) do not fit until all
perimeter seals and hardware is installed and operating. Set and fix door stop ensuring the door
latches freely.
- An installer’s declaration is to be completed by the installer post
installation and fitting of hardware, and returned as confirmation of
compliance with NZS 4520, prior to Hallmark Group supplying of Fire/ID tag
labels.
Maintenance requirements
- Hallmark Fire Doors should be weekly inspected and
maintained to ensure proper functionality.
- Ensure closer and lockset are operational and correctly adjusted.
- Ensure Fire Doors are not held open by any mechanism or
object that will prevent the door from closing or operating in the event of a
fire.
- All seals, hinges, closers, latch set and other hardware should be checked
annually for proper fit and operation, and to ensure all screws and fixings
remain tight.
- Operational clearances should be checked annually to ensure no impairment
to the Fire Door functionality.
- Vision panels can be cleaned with a general glass cleaning
solution. No abrasive materials or products should be used as these will cause
damage to glass surfaces.
- Fire Door surfaces, jambs, seals etc. should be regularly
cleaned with warm water and cloth. No abrasive products should be used as these
can cause damage to painted, stained/lacquered or finished surfaces.
Manufacturer
Legal Trading Name:
Hallmark Group
Business Email:
sales@hallmarkgroup.co.nz
Contact Number/s:
03 3134754 0800 486237
Product Identifier
HFE120DAD
Warnings
This product has no warnings associated with it.
 |
Date last validated:
10 June 2025 |
 |
Date last updated:
10 June 2025 |
|