Compliance Statement
Scope of Use
FIRESTOP Ultra Sealant is designed for use in fire-rated walls, floors, and ceilings where joints, linear gaps, or service penetrations require fire, smoke, and weather sealing. Suitable for use around cables, metal pipes, metal ductwork, and construction joints in plasterboard, masonry, and concrete constructions for both indoor and outdoor applications. The sealant accommodates joint movement up to 20% and is suitable for exposed environments due to its UV and weather resistance. Designed to expand under fire exposure, the sealant forms an intumescent barrier that helps maintain the fire resistance of compartment walls and floors. All installations must comply with tested or assessed systems to AS 1530.4:2014 and AS 4072.1:2005. Refer to firestopcentre.co.nz for FC tech drawings, product information, and test reports.
New Zealand Building Code (NZBC)
The product will, if employed in accordance with the supplier's installation and maintenance requirements, assist with meeting the following provisions of the building code:
Notes
FIRESTOP Ultra has been tested and assessed to AS1430.4:2014 and AS4702.1:2005.
Evidence
The product meets the requirements set out in the following documents, or relevant parts of cited standards within the documents:
FIRESTOP Ultra has been tested and assessed to AS 1530.4:2014 and
AS 4072.1:2005, providing fire resistance ratings (FRR) when applied to
fire-rated substrates in accordance with the relevant tested system, tech drawings and product information.
Please refer to below links.
FIRESTOP Ultra product page
FIRESTOP Ultra BPIR Sheet